NA2XBY

APPLICATION

These power and fixed wiring cables are used in low voltage installation systems. They are well adapted to underground use in industrial applications with an additional mechanical protection. These cables can be fixed on cable trays, within conduits or fixed to walls & where the cable may be subject to mechanical crush and impact.

Construction

Wire Specifications
Conductor Round Stranded Aluminum as per class 2 of IEC 60228
Insulation XLPE applied around the conductor for 90 c
Colors Color: can be supplied on request.
Assembly Cores laid up, filled with non-hygroscopic material, covered with mylar tape and extruded
Armor Galvanized Steel Tape Armor applied as per IEC 60502-1
Sheath PVC Applied for 90 c
Packing Cables to be supplied in wooden drum

Ratings

Wire Specifications
Temperature - 25 C to + 90 C
Voltage 600/1000 V
Applicable Standards IEC 60228, IEC 60502-1
Flame Retardant IEC 60332-1

Conductor Flexibility Class 2 IEC 60228

Rated Voltage 600/1000 V

Minimum Bending Radius (mm) 10 x Overall Diameter

Max conductor Temp in service 90 C

Max. short-circuit temperature: 250°C Minimum installation and handling temperature: 5ºC

Flame retardant IEC 60332-1