Fire Resistant Cu/Mica/XLPE/LSHF
Multi Core Cable with Stranded Copper Conductor
CANDIDATURE
Ideal for static installations, industrial settings, cable ducts, or in-pipe electrical systems. They are widely used outdoors due to strong insulation and flexibility.
La construction
| Chef d'orchestre | Round Stranded Annealed Copper as per class 2 of IEC 60228 with Mica tape applied around |
|---|---|
| Isolation | XLPE appliqué autour du conducteur pour 90c |
| Couleurs | Color: can be supplied on request |
| Fourreau | Low Smoke - HFFR Sheathing Compound PVC |
| Emballage | Cables with CS.A from 1.5 to 4 sqmm to be supplied in coil of 100 meters. Cables with CS.A from 6 to 35 sqmm to be supplied in wooden drum of 1000 meters or 2000 meters |
Notations
| Température | - 25 to+ 70 C |
|---|---|
| Tension | 600/1000 V |
| Normes applicables | IEC 60228, IEC 60502-1 |
| Retardateur de flamme | IEC 60332-1 |

Conductor Flexibility Class 2 IEC 60228

Tension nominale 600/1000 V

Rayon de courbure minimal (mm) 10 x diamètre global

Max conductor Temp 750 - 800 C for 90 minutes in service

Max. short-circuit temperature: 160°C Minimum installation and handling temperature: 5ºC

Retardateur de flamme IEC 60332-1-2